WEM2ELC series residual current operated circuit breaker

Product number:

Summary Description:

WEM2ELC series residual current operated circuit breakers are suitable for low-voltage distribution networks with three-phase four-wire neutral point directly grounded (TT). It is used to provide indirect contact protection; to prevent fire hazard caused by ground fault current due to equipment insulation damage; the well can be used to distribute electric energy and protect the overload and short circuit of the line; it has protection function for overvoltage, undervoltage and phase loss of the line.

Product Parameters Product Sample Certificate
  • Product Parameters
  • Certificate
    • Commodity name: WEM2ELC series residual current operated circuit breaker

    WEM2ELC series residual current operated circuit breakers are suitable for low-voltage distribution networks with three-phase four-wire neutral point directly grounded (TT). It is used to provide indirect contact protection; to prevent fire hazard caused by ground fault current due to equipment insulation damage; the well can be used to distribute electric energy and protect the overload and short circuit of the line; it has protection function for overvoltage, undervoltage and phase loss of the line.

    Main technical parameters

    Shell frame current:125A、250A、400A、630A、800Rated voltage:400V
    Rated current:50~800ARated insulation voltage:1000V
    Number of poles:3P N, 4PFrequency:50HZ
    Rated ultimate short-circuit breaking capacity (Icu):50~65kARated operating short circuit breaking capacity (Ics):35~50kA
    Rated residual operating current I Δn:30mA, 50mA, 100mA, 200mA, 300mA, 400mA, 500mA, 800mA, 1000mA (grading adjustable)Rated impulse withstand voltage (Uimp):12kV
    Function:Rs485 communication, etc.Installation method:N pole on the right (right zero)

     

     

    Working and installation environment

    Ambient temperature:-5 ℃ ~ 40 ℃, and the average value does not exceed 35 ℃

    Atmospheric conditions:The relative humidity of the atmosphere does not exceed 50% when the surrounding air is +40 ℃, and can have higher relative humidity at lower temperature, such as 90% at 20 ℃; Special measures should be taken for condensation occasionally generated by temperature changes

    Altitude:The elevation of the installation site does not exceed 2000m

    Installation category:III

    Pollution level:Level 3

    Usage category:Class B

    Electromagnetic compatibility:The magnetic field strength of the external magnetic field at the installation site in any direction does not exceed 5 times of the geomagnetic field