  • WEL7L小型漏电断路器(修改后白底).png

WEL7L Series Miniature Leakage Circuit Breaker

Product number:

Classification:

Summary Description:

WEL7L series miniature leakage circuit breaker can provide overload, short circuit and leakage protection functions at the same time. It can realize the functions of providing personal protection for indirect contact, supplementary personal protection for direct contact, protection for insulation failure of electrical equipment, simultaneous disconnection of phase line and neutral line, etc., but the neutral line does not provide protection function.

Product Parameters Product Sample Certificate
  • Product Parameters
  • Certificate
    • Commodity name: WEL7L Series Miniature Leakage Circuit Breaker

    WEL7L series miniature leakage circuit breaker can provide overload, short circuit and leakage protection functions at the same time. It can realize the functions of providing personal protection for indirect contact, supplementary personal protection for direct contact, protection for insulation failure of electrical equipment, simultaneous disconnection of phase line and neutral line, etc., but the neutral line does not provide protection function.

    Main technical parameters

    Shell frame current:63ANumber of poles:1P N、2P、3P、3P N、4P
    Rated current:6~63AOvercurrent instantaneous trip type:Type C, Type D
    Rated insulation voltage (Ui):400VRated voltage:

    230V(1P N, 2P),

    400V (3P, 3P N, 4P)

    Rated short circuit capacity:6kARated impulse withstand voltage (Uimp):4kV
    Standard value of rated residual operating current:0.03A, 0.05A, 0.1A (optional).Rated residual inaction current I ▲ no:0.5I▲n
    Rated leakage does not act time:≤ 0.1SRated frequency:50Hz
    Mechanical life:10000 timesElectrical life:6000 times

     

    Working and installation environment

    Ambient temperature:-5 ℃ ~ 40 ℃, and the average value does not exceed 35 ℃

    Atmospheric conditions:The relative humidity of the atmosphere does not exceed 50% at an ambient air temperature of +40°C, and may have a higher relative humidity at lower temperatures, for example up to 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes.

    Altitude:The elevation of the installation site does not exceed 2000m

    Protection class:IP20

    Pollution level:Level 2

    Electromagnetic compatibility:The external magnetic field at the installation site should not exceed 5 times of the geomagnetic field in any direction.

Key words:

Explosion-proof monitoring

Online message