  • WEQ1智能双电源自动转换开关CB级(修改后白底).png

WEQ1 Series Dual Power Automatic Transfer Switch (Class CB)

Product number:

Summary Description:

WEQ1 dual power automatic transfer switch (hereinafter referred to as ATS) is suitable for terminal dual-loop power supply system with AC 50Hz/60Hz, rated working voltage 220V(2P), 380V(3P, 4P) and rated current 10A ~ 63A. The automatic conversion between the common power supply and the standby power supply can be completed to ensure the reliability of the power supply. Mainly used in high-rise buildings, shopping malls and other fire pump, fire smoke machine, elevator, life water pump, accident lighting, evacuation sign light places.

Product Parameters Product Sample Certificate
  • Product Parameters
  • Certificate
    • Commodity name: WEQ1 Series Dual Power Automatic Transfer Switch (Class CB)

    WEQ1 dual power automatic transfer switch (hereinafter referred to as ATS) is suitable for terminal dual-loop power supply system with AC 50Hz/60Hz, rated working voltage 220V(2P), 380V(3P, 4P) and rated current 10A ~ 63A. The automatic conversion between the common power supply and the standby power supply can be completed to ensure the reliability of the power supply. Mainly used in high-rise buildings, shopping malls and other fire pump, fire smoke machine, elevator, life water pump, accident lighting, evacuation sign light places.

    Main technical parameters

    Shell frame current:63ARated voltage:400V
    Rated current:6~63ARated insulation voltage:400V
    Number of poles:3P、4PFrequency:50HZ
    Rated short circuit breaking capacity (Icn):5kARated short-circuit make capacity (peak) Icm:7.65kA
    Conversion method:ATSERated impulse withstand voltage (Uimp):4kV (main circuit), 2.5kV (control circuit)
    Control Type:Ordinary type, Z typeElectrical Level:Class CB

     

    Working and installation environment

    Ambient temperature:-5 ℃ ~ 40 ℃, and the average value does not exceed 35 ℃

    Atmospheric conditions:The relative humidity of the atmosphere does not exceed 50% at an ambient air temperature of +40°C, and may have a higher relative humidity at lower temperatures, for example up to 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes.

    Altitude:The elevation of the installation site does not exceed 2000m

    Usage category:AC-33iB

Key words:

Explosion-proof monitoring

Online message